5.1.9 RTD Configuration (Setpoint Page 9)

Setpoint

Page

Security

Level

Description

Factory Setting

Default

Range

Section

Use NEMA Temp for RTD Values

Disabled

Enabled or Disabled

SP9.1

# of RTD Used for Stator

4

0-6

SP9.2

RTD Voting

Disabled

Enabled or Disabled

SP9.3

Stator Phase A1 Type

Off

120 OHM NI, 100 OHM NI, 100 OHM PT, 10
OHM CU

RTD #1 Description

Stator A1

User defined, Up to 15 Characters

Stator Phase A1 Alarm Level

Off

0-240C (32-464F), Off

Stator Phase A1 Trip Level

Off

0-240C (32-464F), Off

Stator Phase A2 Type

Off

Same as Stator Phase A1

RTD #2 Description

Stator A2

User defined, Up to 15 Characters

Stator Phase A2 Alarm

Off

0-240C (32-464F), Off

Stator Phase A2 Trip Level

Off

0-240C (32-464F), Off

Stator Phase B1 Type

Off

Same as Stator Phase A1

RTD #3 Description

Stator B1

User defined, Up to 15 Characters

Stator Phase B1 Alarm Level

Off

0-240C (32-464F), Off

Stator Phase B1 Trip Level

Off

0-240C (32-464F), Off

Stator Phase B2 Type

Off

Same as Stator Phase A1

RTD #4 Description

Stator B2

User defined, Up to 15 Characters

Stator Phase B2 Alarm Level

Off

0-240C (32-464F), Off

Stator Phase B2 Trip Level

Off

0-240C (32-464F), Off

Stator Phase C1 Type

Off

Same as Stator Phase A1

RTD #5 Description

Stator C1

User defined, Up to 15 Characters

Stator Phase C1 Alarm Level

Off

0-240C (32-464F), Off

Stator Phase C1 Trip Level

Off

0-240C (32-464F), Off

Stator Phase C2 Type

Off

Same as Stator Phase A1

RTD #6 Description

Stator C2

User defined, Up to 15 Characters

Stator Phase C2 Alarm Level

Off

0-240C (32-464F), Off

Stator Phase C2 Trip Level

Off

0-240C (32-464F), Off

End Bearing Type

Off

Same as Stator A1

RTD #7 Description

End Bearing

User defined, Up to 15 Characters

End Bearing Alarm Level

Off

0-240C (32-464F), Off

End Bearing Trip Level

Off

0-240C (32-464F), Off

Shaft Bearing Type

Off

Same as Stator Phase A1

RTD #8 Description

Shaft Bearing

User defined, Up to 15 Characters

Shaft Bearing Alarm Level

Off

0-240C (32-464F), Off

Shaft Bearing Trip Level

Off

0-240C (32-464F), Off

RTD #9 Type

Off

Same as Stator Phase A1

RTD #9 Description

User defined

User defined, Up to 15 Characters

RTD #9 Alarm Level

Off

0-240C (32-464F), Off

RTD #9 Trip Level

Off

0-240C (32-464F), Off

Page

9

RTD Configuratio

n

Level

3

Password Protection

SP9.4