Jksss+ series 2.3 - 4.2kv, Menu – Toshiba VF010H05 User Manual
Page 62
JKSSS+ Series - 56
JKSSS+ Series
2.3 - 4.2KV
SP.6 User I/O Configuration (Setpoint Page 6)
(Security Level: 2)
MENU
PAGE 6 USER I/O
CONFIGURATION
TACHOMETER SCALE
SELECTION: DISABLED
TACH ACCEL TRIP MODE
SELECT: DISABLED
Options: ENABLED or
DISABLED
Options: UNDERSPEED,
OVERSPEED or DISABLED
(Hit DOWN ARROW five times)
MANUAL TACH SCALE
4.0 mA: 0 RPM
TACH RAMP TIME
: 20 SEC
MANUAL TACH SCALE
20.0 mA: 2000 RPM
TACH UNDERSPEED TRIP
PT: 1650 RPM
TACH OVERSPEED TRIP
PT: 1850 RPM
ANALOG OUTPUT #1
:RMS CURRENT
ANALOG OUTPUT #1
4ma: 0
ANALOG OUTPUT #2
:% MOTOR LOAD
ANALOG OUTPUT #2
4mA: 0
ENABLED
Range: 1 - 120 SEC.,
Disabled
Increments of 1
Range: 0 - 3600
Increments of 5
Range: 0 - 3600
Increments of 5
Range:
RPM 0 - 3600
Hottest Bearing 0 - 200°C
Hottest Stator RTD 0 - 200°C
RMS Current 0 - 6500A
% Motor Load 0 - 1000%
KW
0-30000 KW
OFF
Increments of 1
Analog Output
Range
Range: See Analog Output #1
Increments of 1
ANALOG OUTPUT #1
20mA: 250
ANALOG OUTPUT #2
20mA: 1000
Range: 0-65535
Increments of 1
TACH ACCEL TRIP
DELAY: 1 SEC
Range: 1 - 60
Increments of 1
Range: 0-3600
Increments of 5
Range: 0-3600
Increments of 5
Range: 0-65535
Increments of 1
Range: 0-65535
Increments of 1
Range: 0-65535
Increments of 1
USER PROGRAMMABLE
EXTERNAL INPUTS
Continued...