beautypg.com

Caution, Jksss+ series 2.3 - 4.2kv, Cautions – Toshiba VF010H05 User Manual

Page 24

background image

JKSSS+ Series - 18

JKSSS+ Series

2.3 - 4.2KV

Torque Specs for MV Power

Connections

2.8 - Warnings

& Cautions

This section involves working with potentially lethal voltage

levels! Use extreme caution to prevent injury. Pressing “Stop”

push button does not remove AC mains potential.

Do not service this equipment with voltage applied! The unit

can be the source of fatal electric shocks! To avoid shock

hazard, disconnect main power and control power before

working on the unit. Warning labels must be attached to

terminals, enclosure and control panel to meet local codes.

Do not connect the capacitors to the load side (motor side)

of the solid state starter. This will cause di/dt damage to the

SCRs when they are turned on.

Do not connect the capacitors to the input side of the unit.

If you cannot avoid using capacitors across the power lines, they

must be located as far upstream as possible of the input line

contactor. In this situation, optional power factor correction (PFC)

caps contactor should be specified. For additional information and

specifications, please contact the factory.

Never interchange the input and output power connections

on the unit. This will cause excessive voltage to the control circuit

logic.

For bus protection, it is strongly recommended to use non-gap

lightning arrestors in areas where lightning is a significant

problem. The arrestors should be mounted on the nearest utility pole.

2.9 - Medium Voltage Power Connections

Use a properly calibrated torque wrench to tighten all MV connections

according to the chart.

Connections

Cable and wire bundles that enter the controller enclosure should be routed to

avoid interference with moving parts. Minimum bending radius for the type of

cable used should be observed.

Power cables should be braced and/or laced to withstand short circuit forces

wherever such cables are unsupported. Power cables should be adequately sized

to carry the motor full load current in accordance with NEC requirements, and

have an adequate voltage rating. Cables should be dressed and terminated as

appropriate to the voltage class and cable manufacturer’s recommendations.

Main power bus (when provided) and horizontal ground bus are supplied with links

to join shipping sections together. These should be installed in accordance with Fig.

5 through Fig. 7.

All access covers, barriers, partitions, etc. that are temporarily removed during installation

must be replaced.

CAUTION

SCR DAMAGE

Do not connect (PFC) capacitors to the load side of
the unit.

Doing so will cause DI/DT damage to the SCRs when
energized.

!

Bolt

Size

Torque at Full

Engagement

(ft - lbs)

1/4 - 20

6

3/16 - 18

12

3/8 - 16

18

7/16 - 14

30

1/2 - 13

45

9/16 - 12

68

5/8 - 11

90

3/4 - 10

150

7/8 - 9

240

1.0 - 8

245

CAUTION

CAUTION

CAUTION

CAUTION

WARNING

WARNING