JKSSS+ Series - 38

JKSSS+ Series

2.3 - 4.2KV

5.1.4 Relay Assignments (Setpoint Page 4)

1st

2nd

3rd

O/L Trip

Trip Only

None

None

I/B Trip

Trip

None

None

S/C Trip

Trip Only

None

None

Overcurrent Trip

Trip

None

None

Stator RTD Trip

None

None

None

Non Stator RTD Trip

None

None

None

*G/F Hi Set Trip

Trip

None

None

*G/F Lo Set Trip

Trip

None

None

Phase Loss Trip

Trip

None

None

Accel. Time Trip

Trip Only

None

None

Start Curve Trip

Trip Only

None

None

Over Frequency Trip

None

None

None

Under Frequency Trip

Trip

None

None

I*I*T Start Curve

Trip

None

None

Learned Start Curve

Trip

None

None

Phase Reversal

Trip

None

None

Overvoltage Trip

Trip

None

None

Undervoltage Trip

Trip

None

None

Power Factor Trip

None

None

None

Tach Accel Trip

None

None

None

Inhibits Trip

Trip

None

None

Shunt Trip

None

None

None

Bypass Discrepancy

None

None

None

TCB Fault

Trip

None

None

External Input #2

None

None

None

Dual Ramp

None

None

None

Thermostat

Trip

None

None

O/L Warning

Alarm

None

None

Overcurrent Alarm

Alarm

None

None

SCR Fail Shunt Alarm

None

None

None

*Ground Fault Alarm

Alarm

None

None

Under Current Alarm

None

None

None

Motor Running

AUX3

None

None

I/B Alarm

Alarm

None

None

Stator RTD Alarm

None

None

None

Non-Stator RTD Alarm

None

None

None

RTD Failure Alarm

None

None

None

Self Test Fail

Trip

None

None

Thermal Register

Alarm

None

None

U/V Alarm

Alarm

None

None

O/V Alarm

Alarm

None

None

Power Factor Alarm

None

None

None

KW Demand Alarm

None

None

None

KVA Demand Alarm

None

None

None

KVAR Demand Alarm

None

None

None

Amps Demand Alarm

None

None

None

Timed Output

None

None

None

Run Delay Time

None

None

None

At Speed

AUX4

None

None

Range

Section

Factory Setting

Setpoint

Page

Security

Level

Description

Page

4

Relay Assignments

Level

2

Password Protection

None
Trip(AUX1)
Alarm(AUX2)
AUX3
AUX4
AUX5-8
Only Available in 8 Relay
System
Notes:
AUX1 to AUX4 are for Factory
Use only. Do not change!
Only AUX 5 - 8 are used in the
2nd & 3rd relay assignments.

SP4.1