Omron NT-series Programmable Terminal V022-E3-1 User Manual

Page 63

background image

Note

$ '( )*+,

Section 2-6

Converter Unit Connector Specifications

The terminal block specifications of the RS-232C/RS-422A converter unit are indi-
cated here. For details on the method for making the connection cable, refer to
“Making the Cable” (page 272).

NT-AL001 RS-422A terminal block specifications

Connected terminal block RS-422A terminal block (M3 screws)

Electrical characteristics

Conform to EIA RS-422A

Signal direction

Signal input and output is relative to the NT-AL001.

Terminal

Block Pin

Signal Name

Abbreviation

Signal Direction

Block Pin

No.

Signal Name

Abbreviation

Input

Output

8

Request to send (

)

CSA

7

Request to send (

)

CSB

6

Receive data (

)

RDA

5

Receive data (

)

RDB

4

Send data (

)

SDA

3

Send data (

)

SDB

2

Signal ground

SG (GND)

1

Functional ground

* The CSA and CSB signals are for special applications.

Converter Unit Terminal Screws and Crimp Terminals

The terminal screws are M3 screws. Use M3 size crimp terminals. Tighten the ter-
minal screws with a torque of 0.5 N·m.

During wiring, crimp terminals must be used for connections.

[Recommended crimp terminals]

Fork Type

Round Type

6.2mm or less

6.2mm or less

Maker

Type

Recommended Wire Size

Japan Solderless
Terminal MFG

1.25-N3A (Fork)

AWG22 to 18 (0.3 to 0.75mm

2

)

Molex

Y1.25-3.5L (Fork)

AWG22 to 18 (0.3 to 0.75mm

2

)