Publication 1771-6.5.132 - June 2000

Hardware Setup 3-3

Going Online to the PLC-5 Processor

You cannot go online to the PLC-5 processor over DeviceNet. In order
to download and run the example application program in chapter 6
you must use the processor’s RS-232 connector, or download and run
the program via another network.

Chapter 6 provides examples of downloading and running the
application program via ControlNet, Ethernet, and Data Highway Plus
networks. Chapter 5 provides examples of configuring the DeviceNet
network over these networks.

To go online to the PLC-5 processor via ControlNet:

1. Set the PLC-5C ControlNet node address using the two 10-digit

rotary switches on top of the PLC-5C module.

For the example application we used node address 16.

2. Connect the PLC-5C’s ControlNet port to the ControlNet network.

See Appendix B for information on installing and configuring the
ControlNet driver. See the ControlNet 1.5 PLC-5 Programmable
Controller User Manual, publication 1785-6.5.22, for further
information

.

ControlNet PLC-5C processor’s NET address = 16