4

DANGER: Indicates the presence of immediate hazards which will cause severe

personal injury, death or substantial property damage if ignored.

WARNING: Indicates the presence of hazards or unsafe practices which could cause

severe personal injury, death or substantial property damage if ignored.

CAUTION: Indicates the presence of hazards or unsafe practices which could cause

minor personal injury or product or property damage if ignored.

NOTE:

Indicates special instructions on installation, operation, or maintenance which

are important but not related to personal injury hazards.

DANGER: Make sure the gas on which the heater

will operate is the same type as that specified on the

heater rating plate.

WARNING: Should overheating occur or the gas

supply valve fail to shut, do not turn off or disconnect

the electrical supply to the heater. Instead, shut off

the gas supply at a location external to the heater.

WARNING: Do not use this heater if any part has

been under water. Immediately call a qualified

service technician to inspect the heater and to

replace any part of the control system and any gas

control which has been under water.

WARNING: To minimize the possibility of improper

operation, serious personal injury, fire, or damage to

the heater:

Always keep the area around the heater free of

combustible materials, gasoline, and other

flammable liquids and vapors.

Heater should never be covered or have any

blockage to the flow of fresh air to the heater.

WARNING - CALIFORNIA PROPOSITION

65: This product contains chemicals known to the

State of California to cause cancer, birth defects or

other reproductive harm.

WARNING: Risk of electrical shock. More than one

disconnect switch may be required to de-energize

the equipment before servicing.

CAUTION: This heater requires forced water

circulation when the burner is operating. See

minimum and maximum flow rates. Severe damage

will occur if the heater is operated without proper

water flow circulation.

CAUTION: Operation of this heater in low

temperature systems requires special piping.

Harmful internal condensation will occur if the inlet

water temperature does not exceed 120°F. Warranty

claims will be denied when condensation occurs.

CAUTION: If this heater is to be installed above

radiation level, it must be provided with a low water

cut-off device at the time of heater installation.

CAUTION: If this heater is to be installed in a

negative or positive pressure equipment room, there

are special installation requirements. Consult factory

for details.

WARNINGS

Pay Attention to These Terms

NOTE: Minimum 18 AWG, 105°C, stranded wire

must be used for all low voltage (less than 30 volts)

external connections to the unit. Solid conductors

should not be used because they can cause

excessive tension on contact points. Install conduit

as appropriate. All high voltage wires must be the

same size (105°C, stranded wire) as the ones on the

unit or larger.