Freeze Protection

The Raypak electronic temperature control includes a

freeze protection feature. In the event the temperature

drops below 40°F at any of the boiler temperature sen-

sors, the pump is turned on and will remain on until the

temperature at all boiler sensors rises to 45°F.

Controls

The Raypak electronic temperature control is pro-

vided to maintain the desired system water

temperature. The control has various modes of opera-

tion which are described on the following pages.

To minimize short cycling, locate the system (target)

sensor as follows:

Setpoint: The intended system supply temperature.

vent cap can condense as they leave the cap.

Improper location can result in damage to adjacent

structures or building finish. For maximum efficiency

and safety, the following precautions must be

observed:

1. Outdoor models must be installed outdoors and

must use the outdoor vent cap and air intake hood

available from the manufacturer (sales order

option D-11).

2. Periodically check venting system. The heater’s

venting areas must never be obstructed in any

way and minimum clearances must be observed

to prevent restriction of combustion and ventilation

air. Keep area clear and free of combustible and

flammable materials.

3. Do not locate adjacent to any window, door, walk-

way, or gravity air intake. The vent must be

located a minimum of 4 ft horizontally from such

areas.

4. Install above grade level and above normal snow

levels.

5. Vent terminal must be at least 3 ft above any

forced air inlet located within 10 ft.

6. Adjacent brick or masonry surfaces must be pro-

tected with a rust-resistant sheet metal plate.

30

Fig. 29: Outdoor Venting

WARNING: Installation, adjustment and service of

heater controls, including timing of various operating

functions, must be performed by a qualified installer,

service agency or the gas supplier. Failure to do so

may result in control damage, heater malfunction,

property damage, personal injury, or death.

WARNING: Turn off the power to the heater before

installation, adjustment or service of any heater

controls. Failure to do so may result in board

damage, heater malfunction, property damage,

personal injury, or death.

CAUTION: This appliance has provisions to be

connected to more than one supply source. To

reduce the risk of electric shock, disconnect all such

connections before servicing.

CAUTION: Risk of electric shock: More than one

disconnect switch may be required to de-energize

the equipment before servicing.

NOTE: Condensate can freeze on the vent cap.

Frozen condensate on the vent cap can result in a

blocked flue condition.

NOTE: The vent cap and air intake hood must be

furnished by the heater manufacturer in accordance

with its listing (sales order option D-11).