beautypg.com

Water piping, Canadian installations, General – Raypak MVB 5042004 User Manual

Page 12

background image

the enclosure, shall be provided. The openings

shall communicate directly, or by ducts, with the

outdoors or spaces (crawl or attic) that freely com-

municate with the outdoors.

a. Where directly communicating with the out-

doors or where communicating to the

outdoors through vertical ducts, each open-

ing shall have a minimum free area of 1 in.

2

per 4,000 BTUH (550 mm

2

per kW) of total

input rating of all equipment in the enclosure.

b. Where communicating with the outdoors

through horizontal ducts, each opening shall

have a minimum free area of 1 in.

2

per 2,000

BTUH (1,100 mm

2

per kW) of total input rat-

ing of all equipment in the enclosure.

2. One permanent opening, commencing within 12

in. (305 mm) of the top of the enclosure, shall be

permitted where the equipment has clearances of

at least 1 in. (25 mm) from the sides and back and

6 in. (152 mm) from the front of the appliance. The

opening shall directly communicate with the out-

doors or shall communicate through a vertical or

horizontal duct to the outdoors or spaces that

freely communicate with the outdoors, and shall

have a minimum free area of:

a. 1 in.

2

per 3,000 BTUH (740 mm

2

per kW) of

the total input rating of all equipment located in

the enclosure, and

b. Not less than the sum of the areas of all vent

connectors in the confined space.

1. Ventilation of the space occupied by the heater

shall be provided by an opening(s) for ventilation

air at the highest practical point communicating

with the outdoors. The total cross-sectional area of

such an opening(s) shall be at least 10% of the

area required in 2. and 3. (below), but in no case

shall the cross-sectional area be less than 10 in.

2

(65 cm

2

).

12

WARNING: Do not use the “one permanent

opening” method if the equipment room is under

negative pressure conditions.

CAUTION: All combustion air must be drawn from

outside of the building; the mechanical equipment

room must communicate directly with the outdoors.

Canadian Installations

2. For heaters using a barometric damper in the vent

system there shall be a permanent air supply

opening(s) having a cross section area of not less

than 1 in.

2

per 7,000 BTUH (320 mm

2

per kW) up

to and including 1 million BTUH, plus 1 in.

2

per

14,000 BTUH (160 mm

2

per kW) in excess of 1

million BTUH. This opening(s) shall be either

located at or ducted to a point not more than 18 in.

(450 mm) nor less than 6 in. (152 mm) above the

floor level. The duct can also “goose neck” through

the roof. The duct is preferred to be straight down

and terminated 18 in. (450 mm) from the floor, but

not near piping. This air supply opening require-

ment shall be in addition to the air opening for

ventilation air required in 1. (above).

3. For heaters not using a barometric damper in the

vent system, and when air supply is provided by

natural air flow from outdoors for a power burner

and there is no draft regulator, drafthood or similar

flue gas dilution device installed in the same

space, in addition to the opening for ventilation air

required in 1., there shall be a permanent air sup-

ply opening(s) having a total cross-sectional area

of not less than 1 in.

2

for each 30,000 BTUH (74

mm

2

per kW) of total rated input of the burner(s),

and the location of the opening(s) shall not inter-

fere with the intended purpose of the opening(s)

for ventilation air referred to in 1. This opening(s)

can be ducted to a point not more than 18 in. (450

mm) nor less than 6 in. (152 mm) above the floor

level. The duct can also “goose neck” through the

roof. The duct is preferred to be straight down 18

in. (450 mm) from the floor, but not near piping.

4. Refer to the B149 Installation Code for additional

information.

Water Piping

General

The heater should be located so that any water leaks

will not cause damage to the adjacent area or struc-

tures.

WARNING: Care must be taken to ensure that the

equipment room is not under negative pressure

conditions.

NOTE: In lieu of installing the System Temp Sensor

in the system return loop, an alternate system using

a buffer tank (see Fig. 31) can be used for better sys-

tem temperature control.