Air Filter

An air filter is supplied standard with the heater. This

filter is shipped loose for field installation. Refer to the

Air Filter Kit Installation Instructions (Part No. 241338)

for details.

Direct Vent

If outside air is drawn through the intake pipe directly

to the unit for combustion:

1. Install combustion air direct vent in accordance

with Fig. 27 (horizontal) or Fig. 28 (vertical) of this

manual (pages 28 and 29, respectively).

2. Provide adequate ventilation of the space occu-

pied by the heater(s) by an opening(s) for

ventilation air at the highest practical point com-

municating with the outdoors. The total

cross-sectional area shall be at least 1 in.

2

of free

area per 20,000 BTUH (111 mm

2

per kW) of total

input rating of all equipment in the room when the

opening is communicating directly with the out-

doors or through vertical duct(s). The total

cross-sectional area shall be at least 1 in.

2

of free

area per 10,000 BTUH (222 mm

2

per kW) of total

input rating of all equipment in the room when the

opening is communicating with the outdoors

through horizontal duct(s).

3. In cold climates, and to mitigate potential freeze-

up, Raypak highly recommends the installation of

a motorized sealed damper to prevent the circula-

tion of cold air through the heater during the

non-operating hours.

TruSeal™ Combustion Air

In addition to the 3 previous steps, combustion air may

be ducted directly to the heater by using PVC, CPVC

or sealed single-wall galvanized ducting. The duct will

attach directly to the air collar located on the rear of the

heater, using three or four sheet metal screws (not

supplied) equally positioned around the circumference

of the duct. The screen assembly should be removed

before attaching any air duct to the heater. The screws

and duct connection point must be sealed with RTV

(not supplied). TruSeal is generally used when dam-

aging contaminants are present in the mechanical

room.

All ducting must be self-supported.

Conventional Combustion Air

Supply

U.S. Installations

All Air from Inside the Building

The confined space shall be provided with TWO per-

manent openings communicating directly with an

additional room(s) of sufficient volume so that the com-

bined volume of all spaces meets the criteria for a

room large in comparison (NFGC). The total input of all

gas utilization equipment installed in the combined

space shall be considered in making this determina-

tion. Each opening shall have a minimum free area of

1 in.

2

per 1,000 BTUH (2,225 mm

2

per kW) of the total

input rating of all gas utilization equipment in the con-

fined space, but not less than 100 in.

2

(645 cm

2

). One

opening shall commence within 12 in. (305 mm) of the

top, and one opening shall commence within 12 in.

(305 mm) of the bottom of the enclosure. The mini-

mum dimension of air openings shall be not less than

3 in. (76 mm) in any direction.

All Air from Outdoors

The confined space shall communicate with the out-

doors in accordance with one of the methods below.

The minimum dimension of air openings shall not be

less than 3 in. (76 mm) in any direction. Where ducts

are used, they shall be of the same cross-sectional

area as the net free area of the openings to which they

connect.

1. Two permanent openings, one commencing

within 12 in. (305 mm) of the top, and one com-

mencing within 12 in. (305 mm) of the bottom of

CAUTION: Use TruSeal combustion air if

damaging airborne contaminants are or may be

present in the heater area. See the Appendix of this

manual regarding air contamination.

Fig. 8: Air Filter Box