beautypg.com

Gas supp, Gas supply, Electrical power connections – Raypak MVB 5042004 User Manual

Page 20

background image

20

National Electrical Code and any other national,

state, provincial or local codes or regulations hav-

ing jurisdiction.

Safety wiring must be NEC Class 1.

Heater must be electrically grounded as required

by the NEC.

In Canada, CSA C22. 1 C.E.C. Part 1.

The MVB 504-1504 heaters are wired for 120 VAC, 12

amps while the MVB 2004 heaters are wired for 120

VAC, 18 amps. Consult the wiring diagram shipped

with the heater. Before starting the heater, check to

ensure proper voltage to the heater and pump.

Boiler mounted pumps (up to

3

4

hp) get their power

supply directly from the boiler power supply (connec-

tions in rear wiring box). Install a circuit breaker sized

sufficiently for both the heater and the pump. Pumps

larger than

3

4

hp must use a separate power supply

and run the power through the optional pump contac-

tor which is located in the rear wiring box. Use

appropriately-sized wire as defined by NEC, CSA

and/or local codes. All primary wiring should be 125%

of minimum rating.

If any of the original wire as supplied with the heater

must be replaced, it must be replaced with 105°C wire

or its equivalent.

All high voltage wiring connections to the MVB heater

are made inside the rear wiring box as shown in Fig.

18. Pump power should be taken from terminals 2

(Com), 3 (GND) and 6 (Hot) –

3

4

hp and smaller ONLY.

Power to the MVB heater should be connected to ter-

minals 1, 2, and 3 as noted in Fig. 18. All low voltage

wiring, including sensors, interlocks, enable/disable,

and various options are wired into terminals 1–20 on

the front wiring panel as noted in Fig. 18.

When connecting additional gas utilization equipment

to the gas piping system, the existing piping must be

checked to determine if it has adequate capacity for

the combined load.

The gas valve pressure regulator on the heater is

nominally preset as noted in Table J.

During normal operation, carbon dioxide should be 8.5

to 9.0% at full fire for natural gas and between 9.5 and

10.0% for propane gas. Carbon monoxide should be

‹100ppm.

Electrical Power Connections

Installations must follow these codes:

Natural Gas – 1,000 BTU/ft

3

, 0.60 specific gravity at 0.5 in. WC pressure drop

Propane Gas – 2,500 BTU/ft

3

, 1.53 specific gravity at 0.6 in. WC pressure drop

Table I: Maximum Equivalent Pipe Length

NOTE: Manifold pressures should be ±0.2 in. WC.

Table J: Manifold Gas Pressure Settings

Model

No.

1 in. NPT

1-1/4 in. NPT

1-1/2 in. NPT

2 in. NPT

2-1/2 in. NPT

N

P

N

P

N

P

N

P

N

P

504

15

35

65

150

150

360

754

5

15

35

75

70

175

250

1104

15

35

35

75

100

250

225

1504

10

20

20

45

60

150

150

275

2004

35

85

85

200

Model

No.

Manifold Gas Pressure

(High Fire Values)

Natural Gas

Propane Gas

504

-0.1

-0.1

754

-0.4

-0.1

1104

-1.0

-0.2

1504

-2.4

-0.6

2004

-1.0

-0.5

CAUTION: For proper operation, no more than a

30% drop in gas supply pressure from no-load to full-

load conditions is acceptable. Under no

circumstances should the pressure be outside the

listed operational range.