The optional single-try ignition module will lock out

after failing to light one time. To reset it, press and

release the small, recessed black push button located

inside of the cut-out on the lower right-hand corner of

the ignition module case. Turning off the power to

the heater WILL NOT reset the ignition module.

High Limit—Manual Reset

This heater is equipped with a fixed setting manual re-

set high limit temperature device as standard or it may

have an optional adjustable setting manual reset high

temperature device.

The fixed setting manual reset high limit is located on

the In/Out header of the heat exchanger on the right

side of the heater (accessible through the front door

for reset as necessary).

The optional adjustable manual reset high limit is lo-

cated inside the heater junction box. Push the reset

button and adjust the setting to approx. 40°F (20°C)

above desired outlet temperature.

37

Heater Sequence of Operation

If all limits are satisfied and there is a call for heat:

1. The heater pump is powered and begins circulat-

ing water through the heat exchanger.

2. The blower is powered and goes through a 15 sec-

ond prepurge beginning when air flow is proven by

closure of the blower suction air pressure switch.

3. The igniter is powered, and once proven, heats up

for 20 seconds.

4. The gas valve is then energized for a 4 second

trial for ignition period. Trial for ignition is fixed at

50% input. The heater is allowed to modulate once

flame is proven and the firing rate will adjust to

match the load based on the configuration and set-

tings of the temperature control or external input.

5. Once the heat demand is satisfied the gas valve

will close and the blower will run a 30 second post

purge. The heater pump will continue to circulate

water for 0 to 10 minutes depending on the pump

delay setting on the Raypak modulating tempera-

ture control.

Ignition Module

When additional heat is needed, the combustion air

blower starts to purge air from the combustion cham-

ber for 15 seconds. On proof-of-air flow, the

air-proving switch closes and the igniter is energized.

To ensure safe operation, the gas valve cannot open

until the igniter is verified. The main burner is automat-

ically lit when the device is powered and pre-purged.

The heater performs its own safety check and opens

the main valve only after the igniter is proven to be

capable of ignition. The standard ignition module will

attempt to light three times before locking out. To reset

it, turn off power to the heater, wait 30 seconds and re-

apply power.

Fig. 38: Ignition Module

Table U: Ignition Module

Diagnostic LED Flash Codes

Code

Condition

On

System OK; No faults present

Off

Possible control fault; Check power

1 Flash

Low air

2 Flashes

Flame in combustion chamber;

No call for heat

3 Flashes

Ignition lockout

4 Flashes

Low HSI current

5 Flashes

Low 24 VAC

6 Flashes

Internal fault; Replace control