Further advice should be obtained from your pool or

spa builder, accredited pool shop, or chemical suppli-

er for the correct levels for your water.

Automatic Chlorinators and

Chemical Feeders

All chemicals must be introduced and completely dilut-

ed into the pool or spa water before being circulated

through the heater. Do not place sanitizing chemicals

in the skimmer. High chemical concentrations will

result when the pump is not running (e.g. overnight).

Chlorinators must feed downstream of the heater and

have an anti-siphoning device to prevent chemical

back-up into the heater when the pump is shut off.

Gas Supply

Gas piping must have a sediment trap ahead of the

heater gas controls, and a manual shut-off valve lo-

cated outside the heater jacket. It is recommended

that a union be installed in the gas supply piping adja-

cent to the heater for servicing. The gas supply

pressure to the heater must not exceed 10.5 in. WC for

natural gas or 13.0 in. WC for propane gas. A pounds-

to-inches regulator must be installed to reduce the gas

supply pressure if it is higher than noted above. This

regulator should be placed a minimum distance of 10

times the pipe diameter upstream of the heater gas

controls. Refer to Table I for maximum equivalent pipe

lengths.

Gas Supply Connection

NOTE: Failure of a heat exchanger due to lime

scale build-up on the heating surface, low pH or

other chemical imbalance is non-warrantable.

DANGER: Make sure the gas on which the heater

will operate is the same type as specified on the

heater’s rating plate.

CAUTION: The heater must be disconnected from

the gas supply during any pressure testing of the gas

supply system at test pressures in excess of 1/2 psi

(3.45 kPa).

The heater must be isolated from the gas supply pip-

ing system by closing the upstream manual shut-off

valve during any pressure testing of the gas supply

piping system at test pressures equal to or less than

1/2 psi (3.45 kPa). Relieve test pressure in the gas

supply line prior to reconnecting the heater and its

manual shut-off valve to the gas supply line. FAILURE

TO FOLLOW THIS PROCEDURE MAY DAMAGE

THE GAS VALVE. Over-pressurized gas valves are

not covered by warranty. The heater and its gas con-

nections shall be leak-tested before placing the

appliance in operation. Use soapy water for leak test.

DO NOT use an open flame.

Gas Supply Pressure

A minimum of 4.0 in. WC and a maximum of 10.5 in.

WC upstream gas pressure is required under load and

no-load conditions for natural gas. A minimum of 4.0

in. WC and a maximum of 13.0 in. WC is required for

propane gas. The gas pressure regulator(s) supplied

on the heater is for low-pressure service. If upstream

pressure exceeds these values, an intermediate gas

pressure regulator, of the lockup type, must be

installed.

Fig. 17: Gas Supply Connection

CAUTION: Do not use Teflon tape on gas line pipe

thread. A pipe compound rated for use with natural

and propane gases is recommended. Apply

sparingly only on male pipe ends, leaving the two

end threads bare.

CAUTION: Support gas supply piping with

hangers, not by the heater or its accessories. Make

sure the gas piping is protected from physical

damage and freezing, where required.

NOTE:

High chemical concentrates from feeders

and chlorinators that are out of adjustment will cause

rapid corrosion to the heat exchanger. Such damage

is not covered under the warranty.