Table F: Heater Rates of Flow and Pressure Drops

Note: Basis for minimum flow is ∆T. Basis for maximum flow is gpm.

Piping

All high points should be vented. A heater installed

above radiation level must be provided with a low wa-

ter cut-off device (sales order option F-10). This

heater, when used in connection with a refrigeration

system, must be installed so that the chilled medium is

piped in parallel with the heater with appropriate

valves to pre-vent the chilled medium from entering

the heater.

The piping system of a hot water heater connected to

heating coils located in air handling units where they

may be exposed to circulating refrigerated air, must be

equipped with flow control valves or other automatic

means to prevent gravity circulation of the heater

water during the cooling cycle. It is highly recommend-

ed that the piping be insulated.

Air-Separation/Expansion Tank

All heaters should be equipped with a properly sized

expansion tank and air separator fitting as shown in

Fig. 11.

Fig. 11: Air-Separation/Expansion Tank

THERMOSTAT OR

SYSTEM SENSOR

Fig. 12: Single Heater - Low-Temperature (Heat Pump)

Application with Primary/Secondary Piping

THERMOSTAT OR

SYSTEM SENSOR

Fig. 13: Dual Heaters (Reverse/Return)

with Primary/Secondary Piping

Model

No.

Input Output

20° ∆T

30° ∆T

40° ∆T

Min. Flow

Max. Flow

MBTUH

gpm ∆P gpm ∆P gpm ∆P gpm

∆P

∆T gpm

∆P

∆T

504

500

420

42

2.7

28

1.4

25

1.1

34

100

11.3

8

754

750

630

63

6.0

42

2.9

32

1.7

32

1.7

40

100 13.8

13

1104

1100

924

92

13.3

62

6.7

46

4.1

46

4.1

40

113

18.6

16

1504 1500

1260

84

13.3

63

8.0

63

8.0

40

113

22.2

22

2004 1999

1679

112 26.9

84

16.0

84

16.0

40

113

27.2

30

*Maximum 4 times the pipe diameter or 12”, whichever is less.

*Maximum 4 times the pipe diameter or 12”, whichever is less.