Modulating Temperature Control

This heater is equipped with a Raypak modulating

temperature control. Refer to information starting on

page 30 for information on the setting and use of this

control.

Low Water Cut-Off (Optional)

The optional low water cut-off automatically shuts

down the burner whenever water level drops below the

level of the sensing probe. A 5-second time delay pre-

vents premature lockout due to temporary conditions

such as power fluctuations or air pockets.

High & Low Gas Pressure Switches

(Optional)

The optional low gas pressure switch connection

mounts upstream of the gas valve (on the inlet flange

to the gas valve) and is accessible through the remov-

able access panels on the rear of the heater to reset

the gas pressure switch, as necessary. It is used to

ensure that sufficient gas pressure is present for prop-

High Limit—Auto Reset (Optional)

This heater may be equipped with an optional adjust-

able auto reset high limit temperature device.

The optional adjustable auto reset high limit is located

inside the heater junction box. Adjust the setting to

approx. 20°F (10°C) above desired outlet temperature.

Flow Switch

This standard, dual-purpose control, mounted and

wired in series with the main gas valve, shuts off

heater in case of pump failure or low water flow.

Fig. 40: Adjustable High Limit (Auto Reset)

Fig. 41: Flow Switch

Fig. 42: Modulating Temperature Control

Fig. 43: Low Water Cut-Off