Mode 8 – This mode is for remote firing control of the

heater via an external sequencer such as the Raypak

TempTracker MOD+. The Boil Max setting is the

heater shutdown temperature (max temperature). The

heater is enabled via dry contact at the Enable/Disable

connection at the low voltage terminal strip, and the fir-

ing rate is controlled by a 0-10 VDC signal from the

external sequencer. A control signal of ≥0.5 VDC

equates to minimum fire, and a signal of 10 VDC

equates to 100% firing rate.

Definitions

% OUT - Current percent modulation rate of heater.

BOIL DSGN - Design boiler water temperature used in

heat loss calculations.

BOIL MASS - This setting allows adjustment in the

field for high or low thermal masses; High thermal

mass (setting=3) provides slower reaction, lower ther-

mal mass (setting=1) provides faster reaction.

BOIL MAX - Highest outlet water temperature that the

control is allowed to use as a target temperature.

BOIL MIN - Lowest outlet water temperature that the

control is allowed to use as a target temperature.

33

2-10 VDC

4-20 mA*

Boiler Target

0

0

--- (OFF)

1

2

--- (OFF)

2

4

50°F

3

6

71.3°F

4

8

92.5°F

5

10

113.8°F

6

12

135°F

7

14

156.3°F

8

16

177.5°F

9

18

198.8°F

10

20

220°F

Table P: 2-10 VDC or 4-20 mA External Input Signal

*Requires a 500Ω resistor.

NOTE: The defined terms are not active in all

modes of control operation.

BOIL ON - Accumulated runtime of heater (up to 999

hours, then resets to 0).

BOIL OUT - Actual heater outlet water temperature.

BOIL START - Starting boiler water temperature.

BOIL SUP - Actual system supply water temperature.

BOIL TARGET - Target temperature that the heater is

trying to maintain.

‘BURNER’ DELAY - Holds control output at ignition

setting from the start of the ignition sequence to the

specified burner delay time (0 to 3:00 min.).

DEM 1 - Indicates 24 VDC signal has been supplied to

the H+D terminal.

DEM 2 - Indicates 24 VDC Flame Proof signal is pres-

ent.

DIFF - The operating differential of the heater; The

heater outlet water temperature is allowed to rise

above the BOIL TARGET temperature by

1

2

of this dif-

ferential before the heater shuts off. For example, if

the heater target temperature is set to 160°F (71°C)

and the differential is set to 10°F (5°C), on temperature

rise, the heater will shut off at 165°F (74°C). Once the

heater shuts off, it will not come on again until the tem-

perature falls to 155°F (68°C).

*

RAYPAK

MODULATING

TEMP CONTROL

OUTDOOR AIR

SENSOR

*Maximum 4 times the pipe diameter or 12”, whichever is less.

Fig. 36: Mode 8 Primary/Secondary Piping with

External Direct Drive

NOTE: For Modes 7 and 8, connect to pins 13 and

14 on the low-voltage panel. See page 21. Use

these modes for systems using an external signal.