P42-4 Zero Clearance Direct Vent Gas Fireplace

18

The P42 is approved for a 23 ft. (7.0m) vertical, with a maximum 12 ft (3.7m) horizontal offset
using two 90

o

elbows (two 45

o

elbows equal one 90

o

elbow) with rigid pipe vent systems for

Propane and Natural Gas, as per the diagram below.

• No Vent restrictor is required.
• Vent must be supported at offsets

The P42 is approved for a 37 ft. (11.3m) straight
vertical, with rigid pipe vent systems for Propane
and Natural Gas, as per the diagram below.

• Vent restrictor #6 must be used

Diagram 3

Diagram 4

Note: Regency

®

Direct Vent System (Flex) is only approved for horizontal terminations.