P42-4 Zero Clearance Direct Vent Gas Fireplace

15

INSTALLATION

RIGID PIPE VENTING ARRANGEMENTS - HORIZONTAL TERMINATIONS

REGENCY

®

DIRECT VENT SYSTEM (FLEX) (Propane & Natural Gas)

The shaded areas in the diagram show all allowable combinations of vertical runs with horizontal terminations. The chart below shows the
distances with one 90

o

bend (two 45

o

elbows equal one 90

o

elbow). For a second 90

o

bend, see the "Rigid Pipe Venting Arrangements - Horizontal

Terminations" section.

Note: Must use optional rigid pipe adaptor (Part # 510-994)

when using rigid pipe venting systems.

Rigid Pipe Systems:
4"(100mm) inner diameter
6-5/8"(168mm) outer diameter

Regency

®

Flex:

4"(100mm) inner diameter
6-7/8"(175mm) outer diameter

• Rigid Pipe Systems: Maintain a 1-1/4"(32mm) clearance to combustibles

• Regency

®

Flex: Maintain a 1-1/2"(38mm) clearance to combustibles

• Horizontal vent must be supported every 3 feet (0.9 meter)

• Firestops are required at each fl oor level and whenever passing through a wall

A vent guard may be required, check local codes.

Minimum height
requirement

Note: Regency

®

Direct Vent System (Flex) is only approved for horizontal terminations.