50 pound tumbler electrical requirements, Table 12 – Speed Queen Drying Tumblers none User Manual
Page 46
Electrical Requirements
70256801
44
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
50 Pound Tumbler Electrical
Requirements
NOTE: Minimum wire sizes are obtained from the
Canadian Electrical Code and are intended for use
as a guideline only. Electrical connections should be
made only by a qualified electrical contractor in
accordance with all applicable local and national
requirements.
NOTE: Use copper conductors only.
NOTE: Connect to individual branch circuit.
Table 12
Heat Source
Serial Plate Voltage
Terminal Block
Connections
Required
Rated
Current
Breaker
Rating
Breaker
Poles
Recommended
Wire Size
Gas and Steam 120 Volt/60 Hertz/
1 Phase
L1, Neutral and ground
*
20 Amps
1
12 AWG
(3.9 mm
2
)
Gas and Steam 208 or 240 Volt/
60 Hertz/1 Phase
L1, L2, Neutral and
ground
*
15 Amps
2
14 AWG
(2.6 mm
2
)
Gas and Steam 230-240 Volt/50 Hertz/
1 Phase
L1, Neutral and ground†
*
15 Amps
1
14 AWG
(2.6 mm
2
)
Gas and Steam 208 or 240 Volt/
60 Hertz/3 Phase
L1, L2, L3, and ground†
*
15 Amps
3
14 AWG
(2.6 mm
2
)
Gas and Steam 380 or 415 Volt/
50 Hertz/3 Phase
L1, L2, L3 and ground
*
15 Amps
3
14 AWG
(2.6 mm
2
)
Gas and Steam 460-480 Volt/60 Hertz/
3 Phase
L1, L2, L3 and ground
*
15 Amps
3
14 AWG
(2.6 mm
2
)
Electric
240 Volt/50 Hertz/
1 Phase
L1, Neutral and ground
91 Amps
100 Amps
1
2 AWG
(43 mm
2
)
Electric
208 Volt/60 Hertz/
3 Phase
L1, L2, L3 and ground
88 Amps
100 Amps
3
2 AWG
(43 mm
2
)
Electric
240 Volt/60 Hertz/
3 Phase
L1, L2, L3 and ground
78 Amps
90 Amps
3
2 AWG
(43 mm
2
)
Electric
240 Volt/50 Hertz/
3 Phase
L1, L2, L3 and ground
78 Amps
90 Amps
3
2 AWG
(27 mm
2
)
Electric
380 Volt/50 Hertz/
3 Phase
L1, L2, L3 and ground† 50 Amps
60 Amps
3
4 AWG
(27 mm
2
)
Electric
415 Volt/60 Hertz/
3 Phase
L1, L2, L3, and ground† 46 Amps
60 Amps
3
4 AWG
(27 mm
2
)
Electric
480 Volt/60 Hertz/
3 Phase
L1, L2, L3, and ground
38 Amps
50 Amps
3
6 AWG
(17 mm
2
)
*Current Ratings vary slightly depending on model; refer to serial plate.
†MT (manual timer)/CD (rotary coin drop) Models may require a Neutral conductor. Consult wiring diagram.