Profibus interface center, Spc3 – Siemens SPC3 User Manual
Page 64
PROFIBUS Interface Center
SPC3
Page 62
V1.3
SPC3 Hardware Description
2003/04
Copyright (C) Siemens AG 2003. All rights reserved.
Identifier-Related Diagnostics:
For each identifier byte assigned during configuration (for example, 0 x 10 for 1 byte input), a bit is
reserved.
In the case of a modular system with an identifier byte each per module, module-specific diagnostics can be
indicated. One bit respectively will then indicate diagnostics per module.
Bit 7
Bit 6
Bit 5-0
Header Byte
0
1
Block length in bytes including header
Bit Structure
1
1
Identifier Byte 7 has
etc. Identifier Byte 0 has
diagnostics
diagnostics
Channel-Related Diagnostics:
In this block, the diagnosed channels and the diagnostics cause are entered in sequence. Three bits are
required per entry.
Bit 7
Bit 6
Bit 5
Bit 4 - 0
Header Byte
1
0
Identification Number
Channel Number
Coding
Input/Output
Channel Number
Type of Diagnostics
Coding
Channel Type
Coding
Error Type
Coding of the error type is in part manufacturer-specific; other codings are specified in the Standard.
Example:
Status
If the Bit EXT_DIAG is set to 0 , data is viewed as status info from the system view. f.e. cancellation of the
error triggering the diagnostics.
0 0 0 0 0 1 0 0 Device-related diagnostics.
Device-specific
Meaning of the bits
diagnostics field of
is specified
length 3
manufacturer-specific.
0 1 0 0 0 1 0 1 Identifier-related diagnostics.
1 Identification number 0 has diagnostics.
1
1
Identification number 18 has diagnostics.
1 0 0 0 0 0 0 0 Channel-related diagnostics, identification number 0.
0 0 0 0 0 0 1 0 Channel 2.
0 0 0 1 0 1 0 0 Overload, channel organized bit by bit.
1 0 0 0 1 1 0 0 Channel-related diagnostics identification number 12.
0 0 0 0 0 1 1 0 Channel 6.
1 0 1 0 0 1 1 1 Upper limit evalue xceeded, channel organized word by word.