Manitowoc Ice FLAKE/CHIPLET QF0400 User Manual
Page 23
Section 2
Installation Instructions
Part No. 80-1214-3
2-11
Refrigeration System Installation
(QF2200/RFC2085 AND QF2300/RFC2385 ONLY)
USAGE WITH NON-MANITOWOC
CONDENSING UNITS
Manitowoc Condensing Units are specifically designed
for usage with a Manitowoc Flake/Chiplet Ice Machine
Head Sections. Manitowoc Flake/Chiplet Ice Machines
will not operate with non-Manitowoc condensing units.
Factory Equipment Refrigeration Amounts
ICE MACHINE HEAD SECTION
Each ice machine head section ships from the factory
with a R-404A refrigerant charge appropriate for line
sets up to 50’ in length (12.5 lbs.). The serial tag on the
ice machine indicates the refrigerant charge. Additional
refrigerant must be added for line set lengths between
50’ and 100’ (1.5 lbs.).
REMOTE CONDENSING UNIT
Each condensing unit ships from the factory pressurized
with 50/50 nitrogen helium mixture that must be removed
during the installation process (approximately 20 psig).
REFRIGERATION LINE SETS/TRAPS KIT
Refrigeration Rated Tubing and Trap Kits are shipped
capped with atmospheric pressure.
QuietQube®
Ice Machine
Remote Single
Circuit
Condenser
Line Set*
QF2200
QF2300
RFC2085
RFC2385
RC-20
RC-30
RC-50
Line Set
Suction Line
Liquid Line
Insulation
Thickness
RC 20/30/50
3/4 inch
(19.1 mm)
1/2 inch
(12.7 mm)
1/2”(13mm)
Suction Line
1/4” (7mm)
Liquid Line
!
Warning
Installation of a Remote Condensing Unit may require
the use of special equipment for placement. Trained
and qualified personnel are required for proper
rigging and lifting.
! Caution
The 60-month compressor warranty (including the 24-
month labor replacement warranty) will not apply if
the Manitowoc Ice Machine and remote Manitowoc
Condensing Unit are not installed according to
specifications. This warranty also will not apply if the
refrigeration system is modified with a condenser,
heat reclaim device, or other parts or assemblies not
manufactured by Manitowoc Ice, Inc.
! Caution
Never add more than nameplate charge to the
refrigeration system for any application.
!
Warning
Potential Personal Injury Situation
The ice machine head section contains the refrigerant
charge. Installation and brazing of the line sets must be
performed by a properly trained and EPA certified
refrigeration technician aware of the dangers of dealing
with refrigerant charged equipment.
Revised 8/2003