beautypg.com

Manitowoc Ice FLAKE/CHIPLET QF0400 User Manual

Page 130

background image

Refrigeration System

Section 7

7-8

Part No. 80-1214-3

ANALYZING SUCTION PRESSURE

NOTE: Analyze discharge pressure before analyzing suction pressure. High or low discharge pressure may be
causing high or low suction pressure.

Suction Pressure High Checklist

Suction Pressure Low Checklist

NOTE: Do not limit your diagnosis to only the items listed in the checklists.

Possible Cause

Check/Correct

Improper installation

See “Installation/Visual Inspection Checklist”

Discharge pressure

Discharge pressure is too high, and is affecting suction pressure
(See “Freeze Cycle Discharge Pressure High Checklist”

Improper refrigerant charge

Overcharged

Wrong type of refrigerant

Non condensables in system

Other

Non-Manitowoc components in system

TXV flooding (check bulb mounting)

Defective compressor

Possible Cause

Check/Correct

Improper installation

See “Installation/Visual Inspection Checklist”

Discharge pressure

Discharge pressure is too low, and is affecting suction pressure (See “Freeze Cycle
Discharge Pressure Low Checklist”)

Improper refrigerant charge

Undercharged

Wrong type of refrigerant

Other

Non-Manitowoc components in system

Restricted/plugged liquid line drier

Restricted/plugged tubing in suction side of refrigeration system

Expansion valve starving

No water or insufficient pressure

Defective compressor

Moisture in refrigeration system

Dirty Evaporator

Defective Fan Cycle Control

RFC2085/RFC2385 Only - Defe

ctive Head Pressure Control

Revised 8/2003

This manual is related to the following products: