4 insulation resistance test using megger, 5 dielectric strength test, Protective functions – MITSUBISHI ELECTRIC FR-A500L User Manual
Page 46: Daily and periodic inspection
PROTECTIVE FUNCTIONS
35
5.3.4 Insulation resistance test using megger
1) Before performing the insulation resistance test using a megger on the external circuit, disconnect the
cables from all terminals of the inverter so that the test voltage is not applied to the inverter.
2) For the continuity test of the control circuit, use a tester (high resistance range) and do not use the megger
or buzzer.
3) For the inverter, conduct the insulation resistance test on the main circuit only as shown below and do not
perform the test on the control circuit. (Use a 500VDC megger.)
R 1 > S 2 > T 3 > U V M IM Inverter Motor Power DC500V Ground terminal 5.3.5 Dielectric strength test Do not conduct a dielectric strength test. The inverter's main circuit uses semiconductors, which may be Daily and Periodic Inspection Interval Periodic Area of Inspec- tion Inspection Item Description Daily 1 year 2 years Method Criterion Instrument Surrounding Check ambient { (Refer to page 3) Ambient − 10 ° C to +40 ° C, non-freezing. Thermometer, Overall unit Check for unusual { Visual and auditory No fault. General Power Check that main circuit { Measure voltage 1 -L 2 -L 3, >. Within permissible Tester, digital General (1) Check with megger (across main circuit (2) Check for loose screws and bolts. (3) Check for overheat- ing of each part. (4) Clean. { { { { (1) Disconnect all cables from 1 , L 2 , L 3, U, V, W>, and ground terminal (2) Re-tighten. (1) 5M Ω or more. (2), (3) No fault. 500VDC class Conductors, (1) Check conductors for distortion. (2) Check cable sheaths for { { (1), (2) Visual check. (1), (2) No fault. Main Terminal Check for damage. { Visual check. No fault
supply
megger
deteriorated if a pressure test is made.
environment
temperature, humidity,
dust, dirt, etc.
temperature:
Ambient humidity:
90% or less,
non-condensing.
hygrometer,
recorder
vibration and noise.
checks.
supply
voltage
voltage is normal.
across inverter
terminals R-S-T
AC voltage
fluctuation
(Refer to page 40)
multimeter
terminals and
ground terminal).
inverter and
measure across
terminals R, S, T,
U, V, W
with megger.
(3) Visual check.
megger
cables
breakage.
circuit
block