PARAMETERS

22

Func-

tion

Parameter

Number

Name

Setting Range

Minimum

Setting

Increments

Factory Setting

Refer To

Page:

200

Programmed operation minute/second
selection

0 to 3

1

0

131

201

Program set 1
1 to 10

0 to 2: Rotation direction
0 to 400, 9999:Frequency
0 to 99.59: Time

1

0.1Hz

Minute or second

0

9999

0

131

211

Program set 2
11 to 20

0 to 2: Rotation direction
0 to 400, 9999:Frequency
0 to 99.59: Time

1

0.1Hz

Minute or second

0

9999

0

131

221

Program set 3
21 to 30

0 to 2: Rotation direction
0 to 400, 9999:Frequency
0 to 99.59: Time

1

0.1Hz

Minute or second

0

9999

0

131

Program

m

ed operat

ion

231

Timer setting

0 to 99.59



0

131

232

Multi-speed setting (speed 8)

0 to 400Hz, 9999

0.01Hz

9999

135

233

Multi-speed setting (speed 9)

0 to 400Hz, 9999

0.01Hz

9999

135

234

Multi-speed setting (speed 10)

0 to 400Hz, 9999

0.01Hz

9999

135

235

Multi-speed setting (speed 11)

0 to 400Hz, 9999

0.01Hz

9999

135

236

Multi-speed setting (speed 12)

0 to 400Hz, 9999

0.01Hz

9999

135

237

Multi-speed setting (speed 13)

0 to 400Hz, 9999

0.01Hz

9999

135

238

Multi-speed setting (speed 14)

0 to 400Hz, 9999

0.01Hz

9999

135

M

ult

i-s

peed operat

ion

239

Multi-speed setting (speed 15)

0 to 400Hz, 9999

0.01Hz

9999

135

240

Soft-PWM setting

0, 1

1

1

135

Sub f

unc

tions

244

Cooling fan operation selection

0, 1

1

0

135

S

to

p se

le

cti

on

fu

ncti

on

250

Stop selection

0 to 100 sec, 9999

0.1 sec

9999

135

Sub

func

tions

251

Start holding time

0 to 10 sec, 9999

0.1 sec

9999

136

261

Power failure stop selection

0, 1

1

0

137

262

Subtracted frequency at deceleration
start

0 to 20Hz

0.01Hz

3Hz

137

263

Subtraction starting frequency

0 to 120Hz, 9999

0.01Hz

60Hz<50Hz>

137

264

Power-failure deceleration time 1

0 to 3600/

0 to 360 sec

0.1 sec/

0.01 sec

5 sec

137

265

Power-failure deceleration time 2

0 to 3600/

0 to 360 sec, 9999

0.1 sec/

0.01 sec

9999

137

P

ow

er

fa

ilu

re

sto

p fu

ncti

on

266

Power-failure deceleration time switch-
over frequency

0 to 400Hz

0.01Hz

60Hz

137

S

el

ecti

on

fu

ncti

on

270

Stop-on-contact/load torque high-speed
frequency control selection

0, 1, 2, 3

1

0

139

271

High-speed setting maximum current

0 to 200%

0.1%

50%

140

272

Mid-speed setting minimum current

0 to 200%

0.1%

100%

140

273

Current averaging range

0 to 400Hz, 9999

0.01Hz

9999

140

H

igh-s

peed

fr

equenc

y

cont

rol

274

Current averaging filter constant

1 to 4000

1

16

140

275

Stop-on-contact exciting current low-
speed multiplying factor (Note 5)

0 to 1000%, 9999

1%

9999

143

St

op on

cont

ac

t

276

Stop-on-contact PWM carrier frequency
(Note 5)

0, 1, 2, 9999

1

9999

143