INSTALLATION AND WIRING

16

2.2.4 Connection to the PU connector

(1) When connecting the operation panel or parameter unit using a connection cable

• Parameter unit connection cable (FR-CB2) (option) or the following connector and cable.
• Connector: RJ45 connector

Example: 5-554720-3, Nippon AMP

• Cable: Cable conforming to EIA568 (e.g. 10BASE-T cable)

Example: SGLPEV 0.5mm 4P, MITSUBISHI CABLE INDUSTRIES, LTD.

Note: The maximum wiring length is 20m (65.62 feet).

(2) For RS-485 communication

With the operation panel disconnected, the PU connector can be used for communication operation from a
personal computer etc.

Viewed from the inverter (receptacle side) front

SG
P5S
RDA
SDB

SDA
RDB
SG
P5S

Note: 1. Do not connect the PU connector to the computer’s LAN board, FAX modem socket or telephone

modular connector. Otherwise, the product may be damaged due to electrical specification
differences.

2. Pins 2 and 8 (P5S) provide power to the operation unit or parameter unit. Do not use these pins

for RS-485 communication.

Use the connector and cable as detailed below.
• Connector: RJ45 connector

Example: 5-554720-3, Nippon AMP

• Cable: Cable conforming to EIA568 (e.g. 10BASE-T cable)

Example: SGLPEV 0.5mm 4P, MITSUBISHI CABLE INDUSTRIES, LTD.

œWhen the communication board of the personal computer has the RS-232C specifications, prepare an

RS-485, RS-232C converter.

Example of converter.
1) Model: FA-T-RS40

Converter
Industrial Systems Division Mitsubishi Electric Engineering Co., Ltd.

2) Model: DINV-485CAB

Interface built-in cable
Dia Trend Co., Ltd.