beautypg.com

Parameters – MITSUBISHI ELECTRIC FR-A500L User Manual

Page 33

background image

PARAMETERS

23

Func-

tion

Parameter

Number

Name

Setting Range

Minimum

Setting

Increments

Factory Setting

Refer To

Page:

278

Brake opening frequency (Note 3)

0 to 30Hz

0.01Hz

3Hz

142

279

Brake opening current (Note 3)

0 to 200%

0.1%

130%

142

280

Brake opening current detection time
(Note 3)

0 to 2 sec

0.1 sec

0.3 sec

142

281

Brake operation time at start (Note 3)

0 to 5 sec

0.1 sec

0.3 sec

142

282

Brake operation frequency (Note 3)

0 to 30Hz

0.01Hz

6Hz

142

283

Brake operation time at stop (Note 3)

0 to 5 sec

0.1 sec

0.3 sec

142

284

Deceleration detection function selection
(Note 3)

0, 1

1

0

142

Brak

e s

equenc

e f

unc

tions

285

Overspeed detection frequency

0 to 30Hz, 9999

0.01Hz

9999

142

*570

CT/VT Selection

0, 1

1

0

151

900

FM terminal calibration







152

901

AM terminal calibration







152

902

Frequency setting voltage bias

0 to 10V

0 to 60Hz

0.01Hz

0V

0Hz

154

903

Frequency setting voltage gain

0 to 10V

1 to

400Hz

0.01Hz

5V

60Hz

<50Hz>

154

904

Frequency setting current bias

0 to 20mA

0 to 60Hz

0.01Hz

4mA

0Hz

154

C

alibrat

ion f

unc

tions

905

Frequency setting current gain

0 to 20mA

1 to

400Hz

0.01Hz

20mA

60Hz

<50Hz>

154

990

Buzzer control

0, 1

1

1

156

Addit

ional

fu

ncti

on

991

Parameter unit parameters

Refer to the parameter unit instruction manual for details.

Note: 1. Indicates the parameter settings which are ignored when the advanced magnetic flux vector

control mode is selected.

2. The half-tone screened parameters allow their settings to be changed during operation if 0 (factory

setting) has been set in Pr. 77. (Note that the Pr. 72 and Pr. 240 settings cannot be changed
during external operation.)

3. Can be set when Pr. 80, 81

9999, Pr. 60 = 7 or 8.

4. Can be accessed when Pr. 80, 81

9999, Pr. 77 = 801.

5. Can be accessed when Pr. 270 = 1 or 3, Pr. 80, 81

9999.

6. The setting range and min. setting unit will differ according to the Pr. 71 "applied motor" setting

value.

7. Can be accessed when Pr. 29 = 3.
8. Parameters marked asterisk (*) on top are different setting range, factory setting or function from

FR-A540L.

9. Page numbers correspond to A540/A560L instruction manual, IB07401-0x.