beautypg.com

Mote run/stop), 14 how to run/stop the built-in plc function, From outside (remote run/stop) – MITSUBISHI ELECTRIC 700 Series User Manual

Page 95

background image

90

How to RUN/STOP the Built-in PLC Function

from Outside (Remote RUN/STOP)

3.14 How to RUN/STOP the Built-in PLC Function from

Outside (Remote RUN/STOP)

The built-in PLC function is RUN/STOPped by shorting/opening SQ-SD.
Remote RUN/STOP is to RUN/STOP the built-in PLC function from outside the
inverter with SQ-SD shorted (RUN status).
(1) Applications of remote RUN/STOP

In the following cases, the function can be RUN/STOPped by remote operation
using remote RUN/STOP.
1) When the inverter is out of reach.
2) When the inverter in a control box is RUN/STOPped from outside the control box.

(2) Operation performed at remote RUN/STOP

The operation of the sequence program for performing remote RUN/STOP is as
described below.
• Remote STOP.......The function enters the STOP status after the sequence

program is executed up to the END instruction.

• Remote RUN ........When remote RUN is performed after the function has been

put in the "STOP status" by remote STOP, the function
enters the RUN status again and executes the sequence
program from step 0.

(3) Remote RUN/STOP method

There are the following remote RUN/STOP methods.
1) Setting using built-in PLC function parameter (using contact)

Remote RUN/STOP can be performed by turning the remote RUN contact off/on.
For example, this method can be used to STOP the PLC function with the
emergency stop contact.
• When the remote RUN contact turns off, the function enters the "RUN" status.
• When the remote RUN contact turns on, the function enters the "STOP"

status.

Fig 3.21 Timing Chart for RUN/STOP Using Remote RUN Contact

POINT

Setting of remote RUN contact built-in PLC function parameter
X0 to X1F can be set as the remote RUN contacts.
(Refer to the GX Developer manual for details.)

Remote RUN contact
(External input terminal)

OFF

ON

RUN

STOP

Built-in sequence
function:

RUN/STOP status

Step 0

END

Step 0

END

0

STOP status

SQ terminal