beautypg.com

Inverter parameter data read timing chart – MITSUBISHI ELECTRIC 700 Series User Manual

Page 40

background image

35

Inverter Parameter Read/Write Method

1

P

L

C

FU

N

C

TI

O

N

Inverter parameter data read timing chart

Y28(Y2A)
Parameter read
command

X28(X2A)
Parameter read
completion

D9242(D9243)
Parameter
read data

User sequence
processing

Inverter
parameter

1) Read command is turned
on in user sequence.

3) In user sequence, ON of read completion
is confirmed and data are read from data
registers D9242(D9243) and processed.

4) After completion of read,
read command is turned off.

2) Inverter CPU stores inverter parameter
data into data registers D9242(D9243),
and turns on read completion.

5) Inverter CPU confirms that read
command is off and turns off
read completion.