CC-Link I/O Specifications
2
("n" indicates a value determined according to the station number setting.)
*1
Signal names are initial values. Using Pr. 180 to Pr. 186, Pr. 188, and Pr .189, you can
change input signal functions.
Signals of the RYn0, RYn1, and RYn9 can not be changed. Even when changed using Pr.
178, Pr. 179, and Pr. 187, the settings are invalid.
Refer to the inverter manual (applied) for details of Pr. 178 to Pr.189.
*2
Signal names are initial values. Using Pr. 190 to Pr .196, you can change output signal
functions.
Refer to the inverter manual (applied) for details of Pr. 190 to Pr.196.
(2) Remote resister
("n" indicates a value determined according to the station number setting.)
PLC function
device No.
Address
Description
PLC function
device No.
Address
Description
Upper 8
Bits
Lower 8
Bits
RWwn
Monitor
code 2
Monitor
code 1
RWrn
First monitor value
RWwn+1
Set frequency (0.01Hz
increments)
RWrn+1
Second monitor
value
RWwn+2
Link
parameter
expansion
setting
Instruction
code
RWrn+2
Reply
code2
Reply
code1
RWwn+3
Write data
RWrn+3
Read data
D9062
RWwn+4 Registers designed to
read data received
from the master
station
D9078
RWrn+4
Registers designed
to write data to be
sent to the master
station.
D9063
RWwn+5
D9079
RWrn+5
D9064
RWwn+6
D9080
RWrn+6
D9065
RWwn+7
D9081
RWrn+7