Inverter Status Monitoring, Special Registers
for Control
(3) Set frequency (EEPROM) (D9145)
The D9145 data is written to the EEPROM as a set frequency. The unit is 0.01Hz.
(For example, 6000 indicates 60.00Hz.)
When the speed is set, the speed is either 1r/min or 0.1r/min.
The range where the frequency can be set is 0 to 12000 (0 to 120.00Hz).
When the frequency setting is written normally, the write completion signal (X25)
turns on, and at the same time, 0 is set to D9150.
If any value outside the range is written, HFFFF is set to D9150 as soon as the
write completion signal (X25) turns on, resulting in abnormal completion. If
abnormal completion occurs, the set frequency is not changed.
POINT
• Setting is enabled in the PU operation mode and NET operation mode.
(Refer to the Inverter instruction manual (applied).)
CAUTION
When rewriting the set frequency frequently, use device D9144 "set frequency (RAM)".
There are restrictions on the number of write times of the EEPROM. (Approximately
100,000 times)
1000
Set frequency write (E
2
PROM) setting request
Normal write
Abnormal write
Turns on set frequency write
(E
2
PROM) request pulse.
Check whether set frequency
write (E
2
PROM) completion signal
turned on to judge whether write
was performed normally or not.
Stores 1000 (10Hz) into D9145,
and turns on set frequency write
(E
2
PROM) command.
(Until completion signal turns on)