MITSUBISHI ELECTRIC 700 Series User Manual
Page 20
15
Device Map
1
D
e
vi
ce
M
a
p
S
pec
ia
l r
eg
is
ter
s f
o
r co
nt
ro
l
D9133
Output frequency
monitor
Stores the current output frequency.
0.01Hz units
D9134
Output current
monitor
Stores the current output current.
0.01A units
D9135
Output voltage
monitor
Stores the current output voltage.
0.1V units
D9136
Error history 1, 2
Store the errors that occurred in the inverter in order
of occurrence.
D9137
Error history 3, 4
D9138
Error history 5, 6
D9139
Error history 7, 8
D9140
Operation mode
setting read
Stores the current operation mode.
D9141
Set frequency
read (RAM)
Reads and stores the set frequency (RAM).
D9142
Set frequency
read (E
2
PROM)
Reads and stores the set frequency (EEPROM).
D9143
Operation mode
setting write
Sets a new operation mode.
D9144
Set frequency
write (RAM)
Sets the running frequency (RAM).
D9145
Set frequency
write (E
2
PROM)
Sets the running frequency (EEPROM).
D9146
Alarm definition
batch clear
Write H9696 to clear the error history.
D9147
Parameter clear
H9696 write: Parameter clear
H9966 write: All clear
H5A5A write:Parameter clear except communication
parameters
H55AA write:All clear except communication
parameters
During GX Developer communication, perform
clearing by H5A5A or H55AA.
Number
Name
Description
Page