beautypg.com

MITSUBISHI ELECTRIC 700 Series User Manual

Page 21

background image

16

Device Map

S

p

eci

al

r

e

gi

st

er

s f

or

c

on

tr

ol

D9148

Inverter operation
status control

Turn on/off the corresponding bits to control the
inverter operation status.
The initial value: All "0". When M9255 is off, this
device does not function.

31

D9149

Inverter operation
status control
enable/disable
setting

Enable/disable the inverter operation status control
using D9148 and M9200 to M9211 by turning on/off
the corresponding bits.
Bit image is the same as D9148.
The initial value: All "0" (invalid)

32

D9150

Inverter
parameter
access error

Stores the error No. when an error occurs because
the data stored in the parameter or special register is
not reflected on the inverter.

33

D9151

Inverter status

Stores the running status and operating status of the
inverter.

33

D9152

Frequency
setting

0.01Hz units

D9153

Running speed

1(0.1)r/min unit

D9154

Motor torque

0.1% units

D9155

Converter output
voltage

0.1V units

D9156

Regenerative
brake duty

0.1% units

D9157

Electronic thermal
relay function load
factor

0.1% units

D9158

Output current
peak value

0.01A/0.1A units

Number

Name

Description

Page

B15

B12B11

B8B7

B4B3

B0

0:OFF
1:ON

STF
STR
RH
RM
RL
JOG
RT
AU
CS
MRS
STOP
RES

Invalid

B15

B8B7

B4B3

B0

0:OFF
1:ON

Inverter running(RUN)
Forward running
Reverse running
Up to frequency(SU)
Overload alarm(OL)
Instantaneous power failure
/undervoltage(IPF)
Output frequency
detection(FU)
Alarm output(ALM)
Minor fault output(LF)