The branch circuit to be installed on the customer’s power distribution panel must
be a circuit breaker (CB) in compliance with the requirements in Table 5-5. In
addition, follow the guidelines below.

Do not connect other electrical devices to this branch circuit.

Total load of the branch circuit must be under 80–90 percent of the rating.

Prepare a backup circuit to the power distribution panel based on possible device
additions in future.

Locate the device as close as possible to the power distribution panel for ease of
maintenance.

Table 5-5

Requirements for Circuit Breaker on Power Distribution Panel

Router Model

AC Input

DC Input

CB Type

Phase

Rating

CB Type

Phase

Rating

GR2000-2S

15AT

Single

100 V ac, 15A

15AT

Single

200 V ac, 15A

GR2000-4S

15AT

Single

100V ac, 15A

15AT

Single

200V ac, 15A