beautypg.com

C. install wall shield firestops – Hearth and Home Technologies GATEWAY User Manual

Page 20

background image

Heat & Glo • Gateway • 288-900 Rev. W • 10/08

20

Figure 6.3 Firestop Wall Hole

Figure 6.4 Interior Wall Shield Firestop & Termination Cap

C. Install Wall Shield Firestops

For Horizontal Runs - Wall shield fi restops are REQUIRED
on both sides of a combustible wall through which the vent
passes.

To install wall shield fi restops for horizontal runs that pass
through either interior or exterior walls:

• Cut a 7 in. x 8 in. (178 mm x 204 mm) hole through the

wall.

• Position the wall shield fi restops on both sides of the

hole previously cut and secure the wall shield fi restops
with nails or screws.

• Continue the vent run through the wall shield fi restops.

TRIM HEAT SHIELD IF TOO LONG,

ADD TO SHIELD IF TOO SHORT

TERMINATION CAP

WITH BUILT-IN

EXTERIOR FIRESTOP

PV-FS

INTERIOR

FIRESTOP

Note: There must be no insulation or other combustibles
inside the framed wall shield fi restop opening.

PV-FS

FIRESTOP

7 in.

8 in.

If the area above the ceiling is NOT an attic, position and
secure the ceiling fi restop on the ceiling side of the previ-
ously cut and framed hole.

Figure 6.5 Hole & New Framing Members

CEILING

NEW
FRAMING
MEMBERS

EXISTING CEILING
JOISTS

CHIMNEY
HOLE

7 in.

178 mm

8 in.

204 mm

Figure 6.6 Ceiling Firestop (Ceiling Side)

JOIST

PV-FS

CEILING

FIRESTOP

CEILING

NAILS (4 REQUIRED)

• Mark the ceiling to establish the center point of the vent.

• Drill a hole or drive a nail through this center point.

• Check the fl oor above for any obstructions, such as wir-

ing or plumbing runs.

• Reposition the fi replace and vent system, if necessary,

to accommodate the ceiling joists and/or obstructions.

• Cut a 7 in. x 8 in. (178 mm x 204 mm) hole through the

ceiling, using the center point previously marked.

• Frame the hole with framing lumber the same size as

the ceiling joists.

Note: There must be NO INSULATION or other combustibles
inside the framed fi restop opening.

For Vertical Runs - One ceiling fi restop is REQUIRED at
the hole in each ceiling through which the vent passes.

To install fi restops for vertical runs that pass through ceilings:

• Position a plumb bob directly over the center of the ver-

tical vent component.

If the area above the ceiling IS an attic, position and se-
cure the fi restop on top of the previously framed hole. Fig-
ure 6.7 shows an attic installation. Keep insulation away
from the vent pipe at least 1 inch (25 mm).

While it is not mandatory, it is strongly recommended that
an attic insulation shield be used whenever insulation
can come in contact with the vent pipe. Follow your local
building codes.