MVI56E-61850S ♦ ControlLogix Platform

User Manual

IEC 61850 Server Communication Module

Page 66 of 81

ProSoft Technology, Inc.

September 4, 2014

6.1.1 Scrolling LED Status Indicators

The scrolling LED display indicates the module’s operating status as follows:

Initialization Messages

Code

Message

Boot / DDOK

Module is initializing

Ladd

Module is waiting for required module configuration data from
ladder logic to configure the ports

Waiting for Processor Connection

Module did not connect to processor during initialization

Sample ladder logic is not loaded on processor

Module is located in a different slot than the one
configured in the ladder logic

Processor is not in RUN or REM RUN mode

Last config:

Indicates the last date when the module changed its IP
address. You can update the module date and time through
the

Connect to the Module’s Web Page (page 78), or in

MVI56E-61850S controller tags.

Operation Messages
After the initialization step, the following message pattern will be repeated.

Code

Message

OK: Module is communicating with processor
ERR: Module is unable to communicate with processor. For
this scenario, the message above is replaced
with "Processor faulted or is in program mode".

Module IP address

OK: Port is communicating without error
Client/Server Communication Errors: port is having
communication errors. Refer to Diagnostics and
Troubleshooting (page 65) for further information about the
error.