Name

Range

Description

Max Instances

0 to 8

Maximum number of instantiations of this RCB. The matching
Report Control element is generated only if this value is non-
zero.
This number should reflect the number of clients associated to
this report.
The total sum of all values in this column over all lines must
not exceed 8.

Integrity Period

0 to 2,147,483,647

The integrity period for this report in milliseconds, at which the
module will send the report to the client associated to this
report.
This value may be overridden by the 61850 client during the
report-enable sequence.
0 = Disabled

ConfRev

0 to 2,147,483,647

Number of reconfigurations of the report's associated dataset

Buffer Time

0 to 65535

Maximum amount of time, in milliseconds, that buffered events
will be held pending before being reported.

Comment