beautypg.com

61850s identification – ProSoft Technology MVI56E-61850S User Manual

Page 24

background image

Contents

MVI56E-61850S ♦ ControlLogix Platform

User Manual

IEC 61850 Server Communication Module

Page 24 of 81

ProSoft Technology, Inc.

September 4, 2014

3.3

61850S Identification

This section allows you to assign unique IED identification parameters to the module.

Double-click the 61850S

I

DENTIFICATION

icon to edit the parameters.

Name

Description

configVersion

Version of the configuration. It should match attribute "configVersion" of CID's "IED"
element

IED Name

Name of this IED, which must be unique over all IEDs

configRev

Uniquely identifies the configuration the IED. Mapped 61850 to data attribute
LLN0$DC$NamPlt$configRev

Subnet Name

Name of the station "subnetwork" on which this IED resides; meaningful only for SCD files