MVI56E-61850S ♦ ControlLogix Platform

User Manual

IEC 61850 Server Communication Module

Page 22 of 81

ProSoft Technology, Inc.

September 4, 2014

3.1

Backplane Configuration

This section of the configuration describes the database setup and module-level
parameters. Double-click the B

ACKPLANE

C

ONFIGURATION

icon to edit the parameters.

Name

Range

Description

Write Register Count

0 to 4000

For Data DB objects. Number of registers to write
from processor to module. The starting register is
0. This parameter must be set according to the
status and measured data configured through the
[61850S Data DB] section, which is transferred to
the module through the database.

Stale Database Delay

1 to 300000
-1 = Ignore
0 = No delay (issue a
stale-database event
upon detecting failure)

Minimum duration (ms) of backplane I/O failure that
causes the database to be marked stale.

Stale Database Shutdown

Yes/No

Determines whether to shut down the 61850
protocol upon a stale-database event.