Backplane configuration – ProSoft Technology MVI56E-61850S User Manual
Page 22

Contents
MVI56E-61850S ♦ ControlLogix Platform
User Manual
IEC 61850 Server Communication Module
Page 22 of 81
ProSoft Technology, Inc.
September 4, 2014
3.1
Backplane Configuration
This section of the configuration describes the database setup and module-level
parameters. Double-click the B
ACKPLANE
C
ONFIGURATION
icon to edit the parameters.
Name
Range
Description
Write Register Count
0 to 4000
For Data DB objects. Number of registers to write
from processor to module. The starting register is
0. This parameter must be set according to the
status and measured data configured through the
[61850S Data DB] section, which is transferred to
the module through the database.
Stale Database Delay
1 to 300000
-1 = Ignore
0 = No delay (issue a
stale-database event
upon detecting failure)
Minimum duration (ms) of backplane I/O failure that
causes the database to be marked stale.
Stale Database Shutdown
Yes/No
Determines whether to shut down the 61850
protocol upon a stale-database event.