ProSoft Technology MVI56E-61850S User Manual

Page 64

background image

Contents

MVI56E-61850S ♦ ControlLogix Platform

User Manual

IEC 61850 Server Communication Module

Page 64 of 81

ProSoft Technology, Inc.

September 4, 2014

INT

INT[0].

Value

Description

PointID

12

This value must match the corresponding INT Point ID parameter in PCB

Reserved

-

Not used at this time

q

0

0 = Good data, No bit set, 1 = Questionable, Old data bit set
2 = Invalid, Oscillatory bit set, 3 = Old data and oscillatory bits set

EventNumber

-

Not used at this time

t

dd/tt

Date and time, Time-stamp of event

stVal

1000

Data value

REAL

REAL[0].

Value

Description

PointID

13

This value must match the corresponding REAL Point ID parameter in PCB

Reserved

-

Not used at this time

q

0

0 = Good data, No bit set, 1 = Questionable, Old data bit set
2 = Invalid, Oscillatory bit set, 3 = Old data and oscillatory bits set

EventNumber

-

Not used at this time

t

dd/tt

Date and time, Time-stamp of event

stVal

17.17

Data value

5 Verify the acknowledged data in module memory by viewing the MVI56E-61850S

database in the PCB. For more information, see Using the Diagnostics Menu in ProSoft
Configuration Builder

6 In the Diagnostics window, click on 61850 SERVER - DATA MAPPINGS >

Control - Paths & Values. The DO values are displayed here.