MVI56E-61850S ♦ ControlLogix Platform

User Manual

IEC 61850 Server Communication Module

Page 56 of 81

ProSoft Technology, Inc.

September 4, 2014

6 With the processor in RUN mode in RSLogix 5000, locate the

MVI56E61850S.DATA.DATA_DB.Database.WriteData array.

7 Enter arbitrary values in each of the corresponding tags for the Boolean, Integer, and

Real points configured in PCB.

Boolean: MVI56E61850S.DATA.DATA_DB.Database.WriteData[0].0
Integer: MVI56E61850S.DATA.DATA_DB.Database.WriteData[10]
Real: MVI56E61850S.DATA.DATA_DB.Database.WriteData[40] and [41]

8 Enter the Quality value describing the data integrity of each DO. This memory address

corresponds to the DB Quality Offset parameter in PCB above.

Value

61850 Quality Validity

Descripiton

0

Good

No bit set

1

Questionable

Old data bit set

2

Invalid

Oscillatory bit set

3

Invalid

Old data and oscillatory bits set

9 The MVI56E-61850S ladder logic sends these values over the backplane to the MVI56E-

61850S module memory on every scan.

10 Verify the values of the module memory by viewing the MVI56E-61850S database in the

PCB. For more information, see Using the Diagnostics Menu in ProSoft Configuration
Builder