ProSoft Technology MVI56E-61850S User Manual
Page 44

Contents
MVI56E-61850S ♦ ControlLogix Platform
User Manual
IEC 61850 Server Communication Module
Page 44 of 81
ProSoft Technology, Inc.
September 4, 2014
3.11.1 Connecting Your PC to the Module's Ethernet Port
With the module securely mounted, connect one end of the Ethernet cable to the Config
(E1) Port, and the other end to an Ethernet hub or switch accessible from the same network
as your PC. You can also connect directly from the Ethernet Port on your PC to the Config
(E1)
Port on the module by using an Ethernet crossover cable (not included).
Setting Up a Temporary IP Address
Important: ProSoft Configuration Builder locates MVI56E-61850S modules through UDP broadcast messages.
These messages may be blocked by routers or layer 3 switches. In that case, ProSoft Discovery Service will be
unable to locate the modules.
To use ProSoft Configuration Builder, arrange the Ethernet connection so that there is no router/ layer 3 switch
between the computer and the module OR reconfigure the router/ layer 3 switch to allow routing of the UDP
broadcast messages.
1 In the tree view in ProSoft Configuration Builder, select the MVI56E-61850S module.