MVI56E-61850S ♦ ControlLogix Platform

Contents

IEC 61850 Server Communication Module

User Manual

ProSoft Technology, Inc.

Page 53 of 81

September 4, 2014

5

Examples

In This Chapter

Data DB Example ..................................................................................53

SoE Example .........................................................................................58

Control Example ....................................................................................62

This chapter includes examples of setting up the module for Data DB, SoE, and Control data
exchange.

5.1

Data DB Example

This example shows how to set up boolean, integer, and real DB data objects (DO's). In this
section, you will configure the PCB file, edit a data value in RSLogix 5000, and verify the
value has been updated in module memory.

1 In PCB, enter 720 in the Write Register Count parameter value. The module breaks

down this data into blocks of 240 words. Therefore 720 words will cause the module to
generate 3 data blocks to be transferred between the processor and the module.