MVI56E-61850S ♦ ControlLogix Platform

User Manual

IEC 61850 Server Communication Module

Page 60 of 81

ProSoft Technology, Inc.

September 4, 2014

INT

Event[1].

Value

Description

PointID

2

This value must match the corresponding INT Point ID parameter in PCB

Reserved

-

Not used at this time

q

0

0 = Good data, No bit set, 1 = Questionable, Old data bit set
2 = Invalid, Oscillatory bit set, 3 = Old data and oscillatory bits set

EventNumber

-

Not used at this time

t

dd/tt

Date and time, Time-stamp of event

stVal

4321

Data value

REAL

Event[2].

Value

Description

PointID

3

This value must match the corresponding REAL Point ID parameter in PCB

Reserved

-

Not used at this time

q

0

0 = Good data, No bit set, 1 = Questionable, Old data bit set
2 = Invalid, Oscillatory bit set, 3 = Old data and oscillatory bits set

EventNumber

-

Not used at this time

t

dd/tt

Date and time, Time-stamp of event

stVal

99.9

Data value

6 Once these values are populated, enter the number of boolean events to be sent to the

module.

7 To send the data to the module, enter 1 in the

MVI56E61850S.DATA.SOE.BOOL.WriteEvent.Trigger tag. It will reset back to 0 once
triggered.