ProSoft Technology MVI56E-61850S User Manual
Page 60

Contents
MVI56E-61850S ♦ ControlLogix Platform
User Manual
IEC 61850 Server Communication Module
Page 60 of 81
ProSoft Technology, Inc.
September 4, 2014
INT
Event[1].
Value
Description
PointID
2
This value must match the corresponding INT Point ID parameter in PCB
Reserved
-
Not used at this time
q
0
0 = Good data, No bit set, 1 = Questionable, Old data bit set
2 = Invalid, Oscillatory bit set, 3 = Old data and oscillatory bits set
EventNumber
-
Not used at this time
t
dd/tt
Date and time, Time-stamp of event
stVal
4321
Data value
REAL
Event[2].
Value
Description
PointID
3
This value must match the corresponding REAL Point ID parameter in PCB
Reserved
-
Not used at this time
q
0
0 = Good data, No bit set, 1 = Questionable, Old data bit set
2 = Invalid, Oscillatory bit set, 3 = Old data and oscillatory bits set
EventNumber
-
Not used at this time
t
dd/tt
Date and time, Time-stamp of event
stVal
99.9
Data value
6 Once these values are populated, enter the number of boolean events to be sent to the
module.
7 To send the data to the module, enter 1 in the
MVI56E61850S.DATA.SOE.BOOL.WriteEvent.Trigger tag. It will reset back to 0 once
triggered.