ProSoft Technology MVI56-103M User Manual
Page 46

Configuring the MVI56-103M Module
MVI56-103M ♦ ControlLogix Platform
User Manual
IEC 60870-5-103 Master Communication Module
Page 46 of 152
ProSoft Technology, Inc.
February 22, 2013
2.8.6 ASDU Type
This field contains the ASDU type code for the data contained in the message.
1 = Time-tagged message (bit addressed with 2 bits/point)
2 = Time-tagged message with relative time (bit addressed with 2 bits/point)
3 = Measurands I (4 word values using word address using double-word
address)
4 = Time-tagged measurands with relative time (1 float value)
5 = Identification (12 characters using a byte address)
9 = Measurands II (9 word values using word address)
205 = Siemens meter data
2.8.7 Database Index
Database Index is the location in the module's database to use as the source for
the data in the command. Refer to Data Type for specific information on
addressing (page 41).
The data type field determines the meaning of the database index as follows:
Type
Description
DB Index type
6
Clock synchronization
NA
7
General interrogation
NA
20
General Command
Bit address
2.8.8 Function Code
Code
Definition
128
Distance protection
160
Overcurrent protection
176
Transformer differential protection
192
Line Differential protection
133
For SIEMENS ASDU type 205
255
Global function type
x
User-defined
Note: The last item in the Function Code dropdown list is user-defined. If you select U
SER
D
EFINED
from the dropdown list, a text box will appear below the list. You may enter any function code in
this text box that will be accepted by the destination slave.