4 information numbers used in monitor direction – ProSoft Technology MVI56-103M User Manual
Page 124

Reference
MVI56-103M ♦ ControlLogix Platform
User Manual
IEC 60870-5-103 Master Communication Module
Page 124 of 152
ProSoft Technology, Inc.
February 22, 2013
5.8.4 Information Numbers Used in Monitor Direction
System functions
Inf
Description
GI
Type Fun
128
160
176
192
254
255
t(z)
l>>
l
T
l
L
GEN GLB
0
end of general interrogation
8
X
0
time synchronization
6
X
2
reset FCB
5
*
3
reset CU
5
*
4
start/restart
5
*
5
power on
5
*
* - According to main function
Status Indications
Inf
Description
GI
Type Fun
128
160
176
192
254
255
t(z)
l>>
l
T
l
L
GEN GLB
16
auto-recloser active
X
1
X
X
X
17
teleprotection active
X
1
X
X
18
protection active
X
1
X
X
X
X
19
LED reset
1
X
X
X
X
20
monitor direction blocked
X
1
X
X
X
X
21
test mode
X
1
X
X
X
X
22
local parameter setting
X
1
X
X
X
X
23
characteristic 1
X
1
X
24
characteristic 2
X
1
X
25
characteristic 3
X
1
X
26
characteristic 4
X
1
X
27
auxiliary input 1
X
1
X
X
X
X
28
auxiliary input 2
X
1
X
X
X
X
29
auxiliary input 3
X
1
X
X
X
X
30
auxiliary input 4
X
1
X
X
X
X