103m protocol support – ProSoft Technology MVI56-103M User Manual
Page 122

Reference
MVI56-103M ♦ ControlLogix Platform
User Manual
IEC 60870-5-103 Master Communication Module
Page 122 of 152
ProSoft Technology, Inc.
February 22, 2013
5.8
103M Protocol Support
This section describes the portions of IEC 60870-5-103 protocol that are
supported by the module.
Note: Shaded areas are not supported by the module.
5.8.1 List of Type Identification Codes
In Monitor Direction
Type
Description
1
time-tagged message
2
time-tagged message with relative time
3
measurands l
4
time-tagged measurands with relative time
5
identification
6
time synchronization
8
general interrogation termination
9
measurands ll
10
generic data
11
generic identification
23
list of recorded disturbances
26
ready for transmission of disturbance data
27
ready for transmission of channel
28
ready for transmission of tags
29
transmission of tags
30
transmission of disturbance values
31
end of transmission
In Control Direction
Type
Description
6
time synchronization
7
general interrogation
10
generic data
20
general command
21
generic command
24
order for disturbance data transmission
25