Configuring the MVI56-103M Module
MVI56-103M ♦ ControlLogix Platform
User Manual
IEC 60870-5-103 Master Communication Module
Page 38 of 152
ProSoft Technology, Inc.
February 22, 2013
2.5.4 RTS Off
0 to 65535 milliseconds
This parameter sets the number of milliseconds to delay after the last byte of
data is sent before the RTS modem signal will be set low.
2.5.5 Minimum Delay
1 to 60000 milliseconds
This parameter specifies the minimum number of milliseconds to delay before
sending the message (setting RTS high). This can be used when the serial
network requires time for units to turn off their transmitters.
2.5.6 Receive Timeout
1 to 65535 milliseconds
This value represents the number of milliseconds to wait on a port from the time
the first character is received until the last character in the longest message is
received. This parameter will be dependent on the baud rate. A value of 2000
should work with most applications.
2.5.7 Single char ACK F0, 1, or 3
Yes or No
This parameter specifies if the signal E5 character will be used for ACK