ProSoft Technology MVI56-103M User Manual
Page 33

MVI56-103M ♦ ControlLogix Platform
Configuring the MVI56-103M Module
IEC 60870-5-103 Master Communication Module
User Manual
ProSoft Technology, Inc.
Page 33 of 152
February 22, 2013
When sending a General Command, the user might associate the source data
with a register in the MVI56-103M database to be sent to the remote slave. The
following example will send 8 commands to the slave configured as Session
0/Sector 0. When using a General Command, the bit addressing should be used:
# Enable DB Poll Session Sector Data Func Point Ovrd Ovrd
# Code Index Interval Index Index Type Code Index Flag Val
START
1 16000 0 0 0 20 128 16 0 0
1 16016 0 0 0 20 128 17 0 0
1 16032 0 0 0 20 128 18 0 0
1 16048 0 0 0 20 128 19 0 0
1 16064 0 0 0 20 128 23 0 0
1 16080 0 0 0 20 128 24 0 0
1 16096 0 0 0 20 128 25 0 0
1 16112 0 0 0 20 128 26 0 0
END
Refer to the device specification for the Point Index (Information Number) listing
available for control direction.
The module can also send a periodic General Interrogation command in order to
initialize and refresh the event-updated points in its database. The slave keeps a
list of all data subject to General Interrogation.
Step 7: Transfer the Configuration (page 68) from the Computer to the module.