5.4.5 Set ControlLogix Time Block (9970)
Block 9970 identification code requests the module’s date and time. Use this
data to set the PLC clock.
Word Offset in
Block
Data Field(s)
Description
0
Block ID
This field contains the value of 9970 identifying the block type
to the module.
1 to 247
Not Used
Not Used
The module will respond to a valid block 9970 request with a block containing the
requested date and time. The following table describes the format of this block.
Word Offset in
Block
Data Field(s)
Description
0
Reserved
Reserved (0)
1
Block Write ID
This is the next block requested by the module.
2
Year
This field contains the four-digit year for the new time value.
3
Month
This field contains the month value for the new time. Valid
entry for this field is in the range of 1 to 12.
4
Day
This field contains the day value for the new time. Valid entry
for this field is in the range of 1 to 31.
5
Hour
This field contains the hour value for the new time. Valid
entry for this field is in the range of 0 to 23.
6
Minute
This field contains the minute value for the new time. Valid
entry for this field is in the range of 0 to 59.
7
Seconds
This field contains the second value for the new time. Valid
entry for this field is in the range of 0 to 59.
8
Milliseconds
This field contains the millisecond value for the new time.
Valid entry for this field is in the range of 0 to 999.
9 to 248
Not Used
Not Used
249
Block Read ID
This field contains the block identification code of 9970 for
the block.