ProSoft Technology MVI56-103M User Manual
Page 107

MVI56-103M ♦ ControlLogix Platform
Reference
IEC 60870-5-103 Master Communication Module
User Manual
ProSoft Technology, Inc.
Page 107 of 152
February 22, 2013
5.4.3 Event Message Block (9903)
Block identification code 9903 sends event messages received on the Master
port to the processor.
Note: Events are recognized when using a COT = Spontaneous.
Word Offset in
Block
Data Field(s)
Description
0
Reserved
1
Block ID
This is the next block requested by the module.
2
Event Count
This field contains the number of events present in the block.
Values of 1 to 20 are valid.
3 to 12
Event 1
Event message
13 to 22
Event 2
Event message
23 to 32
Event 3
Event message
33 to 42
Event 4
Event message
43 to 52
Event 5
Event message
53 to 62
Event 6
Event message
63 to 72
Event 7
Event message
73 to 82
Event 8
Event message
83 to 92
Event 9
Event message
93 to 102
Event 10
Event message
103 to 112
Event 11
Event message
113 to 122
Event 12
Event message
123 to 132
Event 13
Event message
133 to 142
Event 14
Event message
143 to 152
Event 15
Event message
153 to 162
Event 16
Event message
163 to 172
Event 17
Event message
173 to 182
Event 18
Event message
183 to 192
Event 19
Event message
193 to 202
Event 20
Event message
203 to 248
Spare
Not Used
249
Block ID
This field contains the block identification code of 9903 for the
block.